/Alarms ODB tree: Difference between revisions
mNo edit summary |
Stefan Ritt (talk | contribs) m (→Example) |
||
Line 45: | Line 45: | ||
Type INT 1 4 >99d 0 RWD 3 | Type INT 1 4 >99d 0 RWD 3 | ||
Check interval INT 1 4 >99d 0 RWD 60 | Check interval INT 1 4 >99d 0 RWD 60 | ||
Checked last DWORD 1 4 >99d 0 RWD 0 | |||
Trigger count DWORD 1 4 >99d 0 RWD 0 | |||
Trigger count requirDWORD 1 4 >99d 0 RWD 0 | |||
Checked last DWORD 1 4 >99d 0 RWD 0 | Checked last DWORD 1 4 >99d 0 RWD 0 | ||
Time triggered firstSTRING 1 32 >99d 0 RWD | Time triggered firstSTRING 1 32 >99d 0 RWD | ||
Line 57: | Line 60: | ||
Check interval INT 1 4 >99d 0 RWD 28800 | Check interval INT 1 4 >99d 0 RWD 28800 | ||
Checked last DWORD 1 4 >99d 0 RWD 1058817867 | Checked last DWORD 1 4 >99d 0 RWD 1058817867 | ||
Trigger count DWORD 1 4 >99d 0 RWD 0 | |||
Trigger count requirDWORD 1 4 >99d 0 RWD 0 | |||
Time triggered firstSTRING 1 32 >99d 0 RWD | Time triggered firstSTRING 1 32 >99d 0 RWD | ||
Time triggered last STRING 1 32 >99d 0 RWD | Time triggered last STRING 1 32 >99d 0 RWD | ||
Line 68: | Line 73: | ||
Check interval INT 1 4 19s 0 RWD 60 | Check interval INT 1 4 19s 0 RWD 60 | ||
Checked last DWORD 1 4 19s 0 RWD 1259196026 | Checked last DWORD 1 4 19s 0 RWD 1259196026 | ||
Trigger count DWORD 1 4 >99d 0 RWD 0 | |||
Trigger count requirDWORD 1 4 >99d 0 RWD 0 | |||
Time triggered firstSTRING 1 32 19s 0 RWD Wed Nov 25 12:59:33 2009 | Time triggered firstSTRING 1 32 19s 0 RWD Wed Nov 25 12:59:33 2009 | ||
Time triggered last STRING 1 32 19s 0 RWD Wed Nov 25 16:40:26 2009 | Time triggered last STRING 1 32 19s 0 RWD Wed Nov 25 16:40:26 2009 | ||
Line 85: | Line 92: | ||
Display BGColor STRING 1 32 27h 0 RWD red | Display BGColor STRING 1 32 27h 0 RWD red | ||
Display FGColor STRING 1 32 27h 0 RWD black | Display FGColor STRING 1 32 27h 0 RWD black | ||
Alarm sound BOOL 1 4 27h 0 RWD y | |||
Warning DIR | Warning DIR | ||
Write system messageBOOL 1 4 >99d 0 RWD y | Write system messageBOOL 1 4 >99d 0 RWD y | ||
Line 96: | Line 104: | ||
Display BGColor STRING 1 32 >99d 0 RWD red | Display BGColor STRING 1 32 >99d 0 RWD red | ||
Display FGColor STRING 1 32 >99d 0 RWD black | Display FGColor STRING 1 32 >99d 0 RWD black | ||
Alarm sound BOOL 1 4 27h 0 RWD y | |||
= /Alarms tree structure = | = /Alarms tree structure = |
Latest revision as of 06:55, 19 December 2024
Links
Purpose
The ODB /Alarms tree contains user and system information related to alarms (see Alarm System). The information from this tree is displayed in the Alarms Page.
Creating the /Alarms tree
When the ODB is created, the /Alarms tree is automatically created, with
- two Alarms with <alarm name> "Demo ODB" and "Demo periodic" and
- two Classes with <class name> "Alarm" and "Warning".
These are shown in the example below.
The user may create other alarms and classes by copying an existing <alarm-name> or <alarm-class> subtree and editing (via Alarms Page or odbedit) as required.
By default, the Alarm System is NOT active. When it is active, the overall alarm is checked once every minute. Once the alarm has been triggered, the message associated with the alarm can be repeated at a different rate.
Example
This example (using odbedit) shows the default /Alarms tree. See also Alarms Page.
$ odbedit [local:pol:S]/>cd /alarms [local:pol:S]/Alarms>ls Alarm system active y Alarms Classes
[local:pol:S]/Alarms>ls -r -lt Key name Type #Val Size Last Opn Mode Value --------------------------------------------------------------------------- Alarms DIR Alarm system active BOOL 1 4 4h 0 RWD y Alarms DIR Demo ODB DIR Active BOOL 1 4 >99d 0 RWD n Triggered INT 1 4 >99d 0 RWD 0 Type INT 1 4 >99d 0 RWD 3 Check interval INT 1 4 >99d 0 RWD 60 Checked last DWORD 1 4 >99d 0 RWD 0 Trigger count DWORD 1 4 >99d 0 RWD 0 Trigger count requirDWORD 1 4 >99d 0 RWD 0 Checked last DWORD 1 4 >99d 0 RWD 0 Time triggered firstSTRING 1 32 >99d 0 RWD Time triggered last STRING 1 32 >99d 0 RWD Condition STRING 1 256 >99d 0 RWD /Runinfo/Run number > 100 Alarm Class STRING 1 32 >99d 0 RWD Alarm Alarm Message STRING 1 80 >99d 0 RWD Run number became too large Demo periodic DIR Active BOOL 1 4 >99d 0 RWD n Triggered INT 1 4 >99d 0 RWD 0 Type INT 1 4 >99d 0 RWD 4 Check interval INT 1 4 >99d 0 RWD 28800 Checked last DWORD 1 4 >99d 0 RWD 1058817867 Trigger count DWORD 1 4 >99d 0 RWD 0 Trigger count requirDWORD 1 4 >99d 0 RWD 0 Time triggered firstSTRING 1 32 >99d 0 RWD Time triggered last STRING 1 32 >99d 0 RWD Condition STRING 1 256 >99d 0 RWD Alarm Class STRING 1 32 >99d 0 RWD Warning Alarm Message STRING 1 80 >99d 0 RWD Please do your shift checks fePOL DIR Active BOOL 1 4 19s 0 RWD y Triggered INT 1 4 19s 0 RWD 205 Type INT 1 4 3s 0 RWD 2 Check interval INT 1 4 19s 0 RWD 60 Checked last DWORD 1 4 19s 0 RWD 1259196026 Trigger count DWORD 1 4 >99d 0 RWD 0 Trigger count requirDWORD 1 4 >99d 0 RWD 0 Time triggered firstSTRING 1 32 19s 0 RWD Wed Nov 25 12:59:33 2009 Time triggered last STRING 1 32 19s 0 RWD Wed Nov 25 16:40:26 2009 Condition STRING 1 256 3s 0 RWD Program not running Alarm Class STRING 1 32 19s 0 RWD Caution Alarm Message STRING 1 80 19s 0 RWD Program fePOL is not running Classes DIR Alarm DIR Write system messageBOOL 1 4 27h 0 RWD y Write Elog message BOOL 1 4 27h 0 RWD n System message interINT 1 4 27h 0 RWD 60 System message last DWORD 1 4 27h 0 RWD 0 Execute command STRING 1 256 27h 0 RWD Execute interval INT 1 4 27h 0 RWD 0 Execute last DWORD 1 4 27h 0 RWD 0 Stop run BOOL 1 4 27h 0 RWD n Display BGColor STRING 1 32 27h 0 RWD red Display FGColor STRING 1 32 27h 0 RWD black Alarm sound BOOL 1 4 27h 0 RWD y Warning DIR Write system messageBOOL 1 4 >99d 0 RWD y Write Elog message BOOL 1 4 >99d 0 RWD n System message interINT 1 4 >99d 0 RWD 60 System message last DWORD 1 4 >99d 0 RWD 0 Execute command STRING 1 256 >99d 0 RWD Execute interval INT 1 4 >99d 0 RWD 0 Execute last DWORD 1 4 >99d 0 RWD 0 Stop run BOOL 1 4 >99d 0 RWD n Display BGColor STRING 1 32 >99d 0 RWD red Display FGColor STRING 1 32 >99d 0 RWD black Alarm sound BOOL 1 4 27h 0 RWD y
/Alarms tree structure
The /Alarms ODB tree is split into 2 subtrees:
- Alarms subtree containing as many alarms (i.e. <alarm-name> subtrees) as the user desires. Each alarm must be one of the four defined Alarm Types. These also define the conditions that trigger the alarm.
- Classes subtree containing as many classes (i.e. <class-name> subtrees) as the user desires. Each class defines the action to be taken when the alarm occurs. Two Classes (Alarm and Warning) are defined by default (see Example).
See also Alarm System.
Keys in the /Alarms ODB tree
Alarm system active
- Type: BOOL
- Default: "n"
If this key in the /Alarms ODB tree is set to "y", the alarm system is active. Set to "n" to deactivate.
Alarms subtree
- Type: DIR
Sub-tree in the /Alarms ODB tree defining each individual alarm condition.
<alarm-name> subtree
- Type: DIR
This subtree in the /Alarms/alarms subtree specifies the name of one of the defined alarms, where name is substituted for <alarm-name>. This subtree will be repeated with a different name for each defined alarm.
In the example two <alarm-name> subtrees are shown, called "demo odb" and "demo periodic"
Active
- Type: BOOL
- Default: "n"
If this key in the <alarm-name> subtree is set to "y" , this particular alarm is active.
Triggered
- Type: INT
- Default: 0
If this key in the <alarm-name> subtree is non-zero, this alarm has been triggered. Filled by System.
Type
- Type: INT
- Default:
This key in the <alarm-name> subtree must be one of the listed Alarm Types.
Check interval
- Type: INT
- Default: 60
This key in the <alarm-name> subtree contains the
frequency in seconds at which this alarm condition is to be checked by the alarm system.
Checked last
- Type: DWORD
- Default:
This key in the <alarm-name> subtree is written by the Alarm System.
Time triggered first
- Type: STRING
- Default:
This key in the <alarm-name> subtree is written by the Alarm System.
Time triggered last
- Type: STRING
- Default:
This key in the <alarm-name> subtree is written by the Alarm System.
Condition
- Type: STRING
- Default:
This key in the <alarm-name> subtree contains
the condition on which alarm should trigger for evaluated alarms. See #Evaluated Alarm conditions.
Alarm class
- Type: STRING
- Default:
This key in the <alarm-name> subtree is set to one of the existing Alarm classes, e.g. the defaults "Alarm","Warning" or a user-defined class, e.g. "Caution".
The Alarm class must be defined in the Classes subtree.
Alarm message
- Type: STRING
- Default:
This key in the <alarm-name> subtree constains the message to be written when alarm triggers.
Classes subtree
- Type: DIR
Sub-tree in the /Alarms ODB tree defining each individual alarm class. Each class defines the individual action to be performed by a predefined and requested alarm.
<class-name> subtree
- Type: DIR
This subtree in the Classes subtree defines one of the alarm classes of name name, where name is substituted for <class-name>. This subtree will be repeated with a different name for each defined class. In the example above, two <class-name> subtrees are shown, named "Alarm" and "Warning".
Write System Message
- Type: BOOL
- Default: "y"
If this key in the <class-name> subtree is set to "y", a message will be sent to the System log when an alarm with this alarm class is triggered.
Write Elog Message
- Type: BOOL
- Default: "n"
If this key in the <class-name> subtree is set to "y", a message will be written to the Elog when an alarm with this alarm class is triggered.
System message interval
- Type: INT
- Default: 60
This key in the <class-name> subtree contains the interval in seconds between successive system messages when an alarm with this alarm class is triggered.
Set this key to 0 to ensure that every alarm is recorded into the MIDAS log file.
See important note on the implementation of this key by the alarm system.
System message last
- Type: DWORD
- Default: 0
This key in the <class-name> subtree contains the time when the last alarm system message was written. It is filled by the alarm system.
Execute command
- Type: STRING
- Default: ""
This key in the <class-name> subtree may contain a command to be executed when an alarm with this alarm class is triggered. This parameter can be used to trigger Email or SMS alerts.
Execute interval
- Type: INT
- Default: 0
When an alarm with this alarm class is triggered, if a valid Execute command is supplied, the command will be repeated at an interval in seconds designated by this key in the <class-name> subtree, providing the interval set is greater than 0.
Execute last
- Type: DWORD
- Default: 0
This key in the <class-name> subtree contains the time when the alarm system last executed the command in the key Execute command. It is filled by the alarm system.
Stop run
- Type: BOOL
- Default: "n"
This key in the <class-name> subtree if set to "y" will cause the run to stop when an alarm with this alarm class is triggered.
Display BGColor
- Type: STRING
- Default: "red"
This key in the <class-name> subtree contains the background colour of the alarm banner on the mhttpd Status Page. The alarm banner appears if the alarm is triggered.
Display FGColor
- Type: STRING
- Default: "black"
This key in the <class-name> subtree contains the foreground colour of the alarm banner on the mhttpd Status Page. The alarm banner appears if the alarm is triggered.