/Alarms ODB tree
Purpose
The ODB /Alarms tree contains user and system information related to alarms.
Creating the /Alarms tree
When the ODB is created, two Classes of alarm are created:
- Alarm
- Demo ODB
- Demo Periodic
- Warning
by default, the alarm system is NOT active Currently, the overall alarm is checked once every minute. Once the alarm has been triggered, the message associated with the alarm can be repeated at a different rate.
Example of an /Alarms tree
This /Alarms tree is shown using odbedit (see also mhttpd Alarm page).
$ odbedit [local:pol:S]/>cd /alarms [local:pol:S]/Alarms>ls Alarm system active y Alarms Classes
[local:pol:S]/Alarms>ls -r -lt Key name Type #Val Size Last Opn Mode Value --------------------------------------------------------------------------- Alarms DIR Alarm system active BOOL 1 4 4h 0 RWD y Alarms DIR Demo ODB DIR Active BOOL 1 4 >99d 0 RWD n Triggered INT 1 4 >99d 0 RWD 0 Type INT 1 4 >99d 0 RWD 3 Check interval INT 1 4 >99d 0 RWD 60 Checked last DWORD 1 4 >99d 0 RWD 0 Time triggered firstSTRING 1 32 >99d 0 RWD Time triggered last STRING 1 32 >99d 0 RWD Condition STRING 1 256 >99d 0 RWD /Runinfo/Run number > 100 Alarm Class STRING 1 32 >99d 0 RWD Alarm Alarm Message STRING 1 80 >99d 0 RWD Run number became too large Demo periodic DIR Active BOOL 1 4 >99d 0 RWD n Triggered INT 1 4 >99d 0 RWD 0 Type INT 1 4 >99d 0 RWD 4 Check interval INT 1 4 >99d 0 RWD 28800 Checked last DWORD 1 4 >99d 0 RWD 1058817867 Time triggered firstSTRING 1 32 >99d 0 RWD Time triggered last STRING 1 32 >99d 0 RWD Condition STRING 1 256 >99d 0 RWD Alarm Class STRING 1 32 >99d 0 RWD Warning Alarm Message STRING 1 80 >99d 0 RWD Please do your shift checks
/Alarms tree structure
The Alarms structure is split into 2 sections:
- "Alarms" which define the condition to be tested. The user can create as many Alarms as desired, but each must be one of the four defined Alarm Types .
- "Classes" which define the action to be taken when the alarm occurs. Two Classes (Alarm and Warning) are defined by default. The user can add more Classes as desired.
The four available Alarm Types are shown in the following table. They are defined in midas.h.
Alarm Type | INT value | Explanation
| |
Internal | AT_INTERNAL | 1 | Trigger on internal (program) alarm setting through the use of the al_...() functions.
|
Program | AT_PROGRAM | 2 | Triggered on condition of the state of the defined task.
|
Evaluated | AT_EVALUATED | 3 | Triggered by ODB value on given arithmetical condition.
|
Periodic | AT_PERIODIC | 4 | Triggered by timeout condition defined in the alarm setting.
|
In order to make the system flexible, each alarm class may perform different actions when an alarm is given. For example, it may
- write a system message,
- write to the elog,
- stop the run or
- spawn a detached script listed in the ODB variable /Programs/Classes/Execute command. This feature is used when an Alarm triggers Email or SMS alerts .
Evaluated Alarm conditions
The alarm condition for evaluated alarms is entered into the ODB key /Alarms/Alarms/<alarm_name>/Condition where <alarm_name> is the name of the alarm. See condition key.
The condition may be simply a comparison between any ODB variable and a threshold parameter, e.g.
/Runinfo/Run number > 100
or it may be an evaluated condition. One can write conditions like
/Equipment/HV/Variables/Input[*] < 100
or
/Equipment/HV/Variables/Input[2-3] < 100
to check all values from an array or a certain range. If one array element fulfills the alarm condition, the alarm is triggerrd. In addition, bit-wise alarm conditions are possible, e.g.
/Equipment/Environment/Variables/Input[0] & 8
The alarm is triggered if bit #2 is set in Input[0].
Keys in the /Alarms ODB tree
Alarm system active
- Type: BOOL
- Default: "n"
If this key in the /Alarms ODB tree is set to "y", the alarm system is active. Set to "n" to deactivate.
Alarms subtree
- Type: DIR
Sub-tree in the /Alarms ODB tree defining each individual alarm condition.
<alarm-name> subtree
- Type: DIR
This subtree in the /Alarms/alarms subtree specifies the name of one of the defined alarms. This subtree will be repeated with a different name for each defined alarm.
In the example two <alarm-name> subtrees are shown, called "demo odb" and "demo periodic"
Active
- Type: BOOL
- Default: "n"
If this key in the <alarm-name> subtree is set to "y" , this particular alarm is active.
Triggered
- Type: INT
- Default: 0
If this key in the <alarm-name> subtree is non-zero, this alarm has been triggered. Filled by System.
Type
- Type: INT
- Default:
This key in the <alarm-name> subtree must be one of the listed Alarm Types.
Check interval
- Type: INT
- Default: 60
This key in the <alarm-name> subtree contains the
frequency in seconds at which this alarm condition is to be checked by the alarm system.
Checked last
- Type: DWORD
- Default:
This key in the <alarm-name> subtree is written by the Alarm System.
Time triggered first
- Type: STRING
- Default:
This key in the <alarm-name> subtree is written by the Alarm System.
Time triggered last
- Type: STRING
- Default:
This key in the <alarm-name> subtree is written by the Alarm System.
Condition
- Type: STRING
- Default:
This key in the <alarm-name> subtree contains
the condition on which alarm should trigger.
Alarm class
- Type: STRING
- Default:
This key in the <alarm-name> subtree is set to one of the existing Alarm classes, e.g. "Alarm","Warning".
Alarm message
- Type: STRING
- Default:
This key in the <alarm-name> subtree constains the message to be written when alarm triggers.
Classes
DIR
Sub-tree defining each individual action to be performed by a pre-defined and requested alarm.
Warning
DIR
Name of one of the defined classes
Write System Message
BOOL
If set to "y" a message will be sent to the System log when alarm is triggered.
Write Elog Message
BOOL
If set to "y" a message will be written to the Elog when alarm is triggered
System message interval
INT
Interval in seconds between successive system messages when alarm is triggered
System message last
DWORD
Filled by System...
Execute command
STRING
Command to be executed when alarm is triggered.
Execute last
DWORD
Stop run
BOOL
Display BGColor
STRING
Background colour of alarm banner (mhttpd only).
Display FGColor
STRING
Foreground colour of alarm banner (mhttpd only).
Examples of an /Alarms tree
Part of the /Alarms tree is shown below using odbedit (see also mhttpd Alarm page).
[local:pol:S]/>cd /alarms [local:pol:S]/Alarms>ls Alarm system active y Alarms Classes Some of the types of alarm under the /Alarms/Alarms tree for an experiment are shown below:
[local:pol:S]/Alarms>ls -r -lt Key name Type #Val Size Last Opn Mode Value
Alarms DIR
Alarm system active BOOL 1 4 4h 0 RWD y Alarms DIR Demo ODB DIR Active BOOL 1 4 >99d 0 RWD n Triggered INT 1 4 >99d 0 RWD 0 Type INT 1 4 >99d 0 RWD 3 Check interval INT 1 4 >99d 0 RWD 60 Checked last DWORD 1 4 >99d 0 RWD 0 Time triggered firstSTRING 1 32 >99d 0 RWD Time triggered last STRING 1 32 >99d 0 RWD Condition STRING 1 256 >99d 0 RWD /Runinfo/Run number > 100 Alarm Class STRING 1 32 >99d 0 RWD Alarm Alarm Message STRING 1 80 >99d 0 RWD Run number became too large Demo periodic DIR Active BOOL 1 4 >99d 0 RWD n Triggered INT 1 4 >99d 0 RWD 0 Type INT 1 4 >99d 0 RWD 4 Check interval INT 1 4 >99d 0 RWD 28800 Checked last DWORD 1 4 >99d 0 RWD 1058817867 Time triggered firstSTRING 1 32 >99d 0 RWD Time triggered last STRING 1 32 >99d 0 RWD Condition STRING 1 256 >99d 0 RWD Alarm Class STRING 1 32 >99d 0 RWD Warning Alarm Message STRING 1 80 >99d 0 RWD Please do your shift checks fePOL DIR Active BOOL 1 4 19s 0 RWD y Triggered INT 1 4 19s 0 RWD 205 Type INT 1 4 3s 0 RWD 2 Check interval INT 1 4 19s 0 RWD 60 Checked last DWORD 1 4 19s 0 RWD 1259196026 Time triggered firstSTRING 1 32 19s 0 RWD Wed Nov 25 12:59:33 2009 Time triggered last STRING 1 32 19s 0 RWD Wed Nov 25 16:40:26 2009 Condition STRING 1 256 3s 0 RWD Program not running Alarm Class STRING 1 32 19s 0 RWD Caution Alarm Message STRING 1 80 19s 0 RWD Program fePOL is not running thr2 trip DIR Active BOOL 1 4 3s 0 RWD y Triggered INT 1 4 3s 0 RWD 0 Type INT 1 4 3s 0 RWD 3 Check interval INT 1 4 3s 0 RWD 15 Checked last DWORD 1 4 3s 0 RWD 1259196042 Time triggered firstSTRING 1 32 3s 0 RWD Time triggered last STRING 1 32 3s 0 RWD Condition STRING 1 256 3s 0 RWD /Equipment/Info ODB/Variables/last failed thr test = 2 Alarm Class STRING 1 32 3s 0 RWD Threshold Alarm Message STRING 1 80 3s 0 RWD Laser threshold check failed
In the above example,
Demo odb and Demo periodic were created when the ODB was created. The alarm Fepol was added automatically when the user filled the alarm class field in the /Programs/fepol sub-tree. The other alarm thr2_trip was added by the user. Four Classes of alarms (Alarm, Caution, Warning and Threshold) are defined under the /Alarms/Classes tree for this experiment. Alarm and Warning were created when the ODB was created. The user added two more classes, Caution and Threshold, by copying and editing one of the existing classes. The Classes defined for the experiment are shown below:
Classes DIR Alarm DIR Write system messageBOOL 1 4 27h 0 RWD y Write Elog message BOOL 1 4 27h 0 RWD n System message interINT 1 4 27h 0 RWD 60 System message last DWORD 1 4 27h 0 RWD 0 Execute command STRING 1 256 27h 0 RWD Execute interval INT 1 4 27h 0 RWD 0 Execute last DWORD 1 4 27h 0 RWD 0 Stop run BOOL 1 4 27h 0 RWD n Display BGColor STRING 1 32 27h 0 RWD red Display FGColor STRING 1 32 27h 0 RWD black Warning DIR Write system messageBOOL 1 4 >99d 0 RWD y Write Elog message BOOL 1 4 >99d 0 RWD n System message interINT 1 4 >99d 0 RWD 60 System message last DWORD 1 4 >99d 0 RWD 0 Execute command STRING 1 256 >99d 0 RWD Execute interval INT 1 4 >99d 0 RWD 0 Execute last DWORD 1 4 >99d 0 RWD 0 Stop run BOOL 1 4 >99d 0 RWD n Display BGColor STRING 1 32 >99d 0 RWD red Display FGColor STRING 1 32 >99d 0 RWD black Caution DIR Write system messageBOOL 1 4 19s 0 RWD y Write Elog message BOOL 1 4 19s 0 RWD n System message interINT 1 4 19s 0 RWD 60 System message last DWORD 1 4 19s 0 RWD 1259196026 Execute command STRING 1 256 19s 0 RWD Execute interval INT 1 4 19s 0 RWD 0 Execute last DWORD 1 4 19s 0 RWD 0 Stop run BOOL 1 4 19s 0 RWD y Display BGColor STRING 1 32 19s 0 RWD blue Display FGColor STRING 1 32 19s 0 RWD red Threshold DIR Write system messageBOOL 1 4 >99d 0 RWD n Write Elog message BOOL 1 4 >99d 0 RWD n System message interINT 1 4 >99d 0 RWD 60 System message last DWORD 1 4 >99d 0 RWD 0 Execute command STRING 1 256 >99d 0 RWD Execute interval INT 1 4 >99d 0 RWD 0 Execute last DWORD 1 4 >99d 0 RWD 0 Stop run BOOL 1 4 >99d 0 RWD n Display BGColor STRING 1 32 >99d 0 RWD yellow Display FGColor STRING 1 32 >99d 0 RWD black
Alarm triggers Email or SMS alerts
It is also possible to have the MIDAS alarm system send email or SMS alerts to cell phones when alarms are triggered. This can be configured by defining an ODB alarm on a critical ODB parameter, e.g.
/Alarms/Alarms/Liquid Level Active y Triggered 0 (0x0) Type 3 (0x3) Check interval 60 (0x3C) Checked last 1227690148 (0x492D10A4) Time triggered first (empty) Time triggered last (empty) Condition /Equipment/Environment/Variables/Input[0] < 10 Alarm Class Level Alarm Alarm Message Liquid Level is only %s In this example, the alarm triggers an alarm of class "Level Alarm". This alarm class is defined as follows:
/Alarms/Classes/Level Alarm Write system message y Write Elog message n System message interval 600 (0x258) System message last 0 (0x0) Execute command /home/midas/level_alarm '%s' Execute interval 1800 (0x708) Execute last 0 (0x0) Stop run n Display BGColor red Display FGColor black The key here is to call a script "level_alarm", which can send emails. Use something like:
- /bin/csh
echo $1 | mail -s \"Level Alarm\" your.name@domain.edu odbedit -c 'msg 2 level_alarm \"Alarm was sent to your.name@domain.edu\"' The second command just generates a MIDAS system message for confirmation. Most cell phones (depends on the provider) have an email address. If you send an email there, it will be translated into a SMS message.
The script file above can of course be more complicated. A perl script could be used that parses an address list, so other interested parties can register by adding his/her email address to that list. The script may also collects some other slow control variables (like pressure, temperature) and combine them into the SMS message.
For very sensitive systems, having an alarm via SMS may not be sufficient, since the alarm system could be down (e.g. computer crash, network failure). In this case 'negative alarms' can be used. For example, every 30 minutes the system may send an SMS with the current parameter values. If the expected message is not received, it may indicate that something in the MIDAS system is wrong.
Implementation of the MIDAS Alarm System
Alarms are checked inside alarm.c::al_check(). This function is called by cm_yield() every 10 seconds and by rpc_server_thread(), also every 10 seconds. For remote MIDAS clients, their al_check() issues an RPC_AL_CHECK RPC call into the MIDAS server utility mserver, where rpc_server_dispatch() calls the local al_check(). As result, all alarm checks run inside a process directly attached to the local MIDAS shared memory (inside a local client or inside an mserver process for a remote client). Each and every MIDAS client runs the alarm checks. To prevent race conditions between different MIDAS clients, access to al_check() is serialized using the ALARM semaphore. Inside al_check(), alarms are triggered using al_trigger_alarm(), which in turn calls al_trigger_class(). Inside al_trigger_class(), the alarm is recorded into an elog or into midas.log using cm_msg(MTALK).
Special note should be made of the ODB setting "/Alarm/Classes/xxx/System message interval", which has a surprising effect - after an alarm is recorded into system messages (using cm_msg(MTALK)), no record is made of any subsequent alarms until the time interval set by this variable elapses. With default value of 60 seconds, after one alarm, no more alarms are recorded for 60 seconds. Also, because all the alarms are checked at the same time, only the first triggered alarm will be recorded.
As of alarm.c rev 4683, "System message interval" is set to 0 ensures that every alarm is recorded into the MIDAS log file. (In previous revisions, this setting may still miss some alarms).
There are 3 types of alarms:
1) "program not running" alarms.
These alarms are enabled in ODB by setting /Programs/ppp/Alarm class. Each time al_check() runs, every program listed in /Programs is tested using "cm_exist()" and if the program is not running, the time of first failure is remembered in /Programs/ppp/First failed.
If the program has not been running for longer than the time set in ODB key /Programs/ppp/Check interval, an alarm is triggered (if enabled by /Programs/ppp/Alarm class and the program is restarted (if enabled by /Programs/ppp/Auto restart).
The "not running" condition is tested every 10 seconds (each time al_check() is called), but the frequency of "program not running" alarms can be reduced by increasing the value of /Alarms/Alarms/ppp/Check interval (default value 60 seconds). This can be useful if System message interval is set to zero.
2) "evaluated" alarms
3) "periodic" alarms
There is nothing surprising in these alarms. Each alarm is checked with a time period set by /Alarm/xxx/Check interval. The value of an evaluated alarm is computed using al_evaluate_condition().