Equipment List Parameters: Difference between revisions
No edit summary |
|||
Line 1: | Line 1: | ||
== | == Explanation of Equipment List Parameters == | ||
Links | Links | ||
Line 11: | Line 11: | ||
[[#MirroredInODB]] | [[#MirroredInODB]] | ||
''' | ==Introduction== | ||
The Equipment declaration in the frontend uses the EQUIPMENT structure defined in ''midas.h'' in the MIDAS package. Only those fields that are needed by the frontend are | |||
included (see example below). Some of these parameters are copied to the ODB <span style="color: purple;">''/Equipment/<equipment-name>/Common''</span> subdirectory when the frontend is initialized. | |||
Each of the parameters found in the frontend Equipment Declaration are described below. | |||
==Example Equipment declaration in a frontend == | |||
An example of an Equipment declaration in a frontend is shown below: | |||
/*-- Equipment list ------------------------------------------------*/ | |||
EQUIPMENT equipment[] = { | |||
{"Trigger", /* equipment name */ | |||
{1, 0, /* event ID, trigger mask */ | |||
"SYSTEM", /* event buffer */ | |||
EQ_POLLED, /* equipment type */ | |||
LAM_SOURCE(0, 0xFFFFFF), /* event source crate 0, all stations */ | |||
"MIDAS", /* format */ | |||
TRUE, /* enabled */ | |||
RO_RUNNING | /* read only when running */ | |||
RO_ODB, /* and update ODB */ | |||
100, /* poll for 100ms */ | |||
0, /* stop run after this event limit */ | |||
0, /* number of sub events */ | |||
0, /* don't log history */ | |||
"", "", "",}, | |||
read_trigger_event, /* readout routine */ | |||
}, | |||
* If this field is left empty, (i.e. set to ""), the readout function associated with that equipment will still be performed, but the actual event won't be sent to the buffer. Instead, that particular equipment can be | {"Scaler", /* equipment name */ | ||
{2, 0, /* event ID, trigger mask */ | |||
"SYSTEM", /* event buffer */ | |||
EQ_PERIODIC | EQ_MANUAL_TRIG, /* equipment type */ | |||
0, /* event source */ | |||
"MIDAS", /* format */ | |||
TRUE, /* enabled */ | |||
RO_RUNNING | RO_TRANSITIONS | /* read when running and on transitions */ | |||
RO_ODB, /* and update ODB */ | |||
10000, /* read every 10 sec */ | |||
0, /* stop run after this event limit */ | |||
0, /* number of sub events */ | |||
0, /* log history */ | |||
"", "", "",}, | |||
read_scaler_event, /* readout routine */ | |||
}, | |||
{""} | |||
}; | |||
== EQUIPMENT Structure parameters == | |||
===Equipment Name=== | |||
Each equipment has to be assigned a unique Name. The name will be the reference name of the equipment generating the event. Examples of typical equipment Names are "Trigger","Scaler","Epics". | |||
===EventID=== | |||
Each equipment has to be associated with a unique event ID . The event ID will be part of the event header of that particular equipment. | |||
===TriggerMask=== | |||
If the equipment [[#Type|Type]] is [[#EQ_INTERRUPT|EQ_INTERRUPT]] or [[#EQ_MULTITHREAD|EQ_MULTITHREAD]], each equipment must be associated with a unique Trigger Mask In this case, the Trigger Mask can be modified dynamically by the readout routine to define a [[subevent type]] on an event-by-event basis. This can be used to mix "physics events" (from a physics trigger) and "calibration events" (from a clock for example) in one run and identify them later. Both parameters are declared as 16-bit values. If the Trigger Mask is used in a single bit-wise mode, 16 is the maximum number of different masks available. | |||
<div id="MirroredInODB"></div> | |||
===Buffer=== | |||
Specifies the name of the Buffer to which the event will be sent. After composition of an equipment, the Midas [[Frontend Operation#Frontend|Frontend]] ''mfe.c'' | |||
takes over the sending of this event to the buffer (usually the SYSTEM buffer) on the back-end computer where it may be sent to the data logger [([mlogger]]) and the [[analyser]]. | |||
* If this field is left empty, (i.e. set to ""), the readout function associated with that equipment will still be performed, but the actual event won't be sent to the buffer. Instead, that particular equipment can be mirrored in the ODB if the [[#RO_ODB|RO_ODB]] flag is turned on (see @ref FE_RO_ODB_example "example"). The ODB is updated with a new event approximately every second. Note that this feature is generally used only for testing or monitoring, as writing large amounts of data to the ODB takes time. | |||
* By using a buffer other than the SYSTEM buffer, [[Event Filtering]] can be implemented. | * By using a buffer other than the SYSTEM buffer, [[Event Filtering]] can be implemented. | ||
* If using an [[Event Builder | * If using an [[Event Builder]] ( i.e. a secondary stage on the back-end to collect and assemble events coming from different buffers in order to compose a larger event) , a dedicated buffer can be specified. In this case the [[#EQ_EB|EQ_EB]] flag must be turned on, and the events coming from the [[Frontend Operation#Frontend|Frontend]] are called ''fragments''. | ||
compose a larger event) , a dedicated buffer can be specified. In this case the [[#EQ_EB|EQ_EB]] flag must be turned on, and the events coming from the [[Frontend Operation#Frontend|Frontend]] are called ''fragments''. | |||
===Type=== | |||
Type specifies the type of equipment, and should be set to one of the Equipment Flags EQ_XXX selected from the [[Equipment Flags|list of valid Equipment Flags]], i.e. one of | |||
from the [[Equipment Flags|list of valid Equipment Flags]], i.e. one of | |||
<div style="column-count:4;-moz-column-count:4;-webkit-column-count:4"> | <div style="column-count:4;-moz-column-count:4;-webkit-column-count:4"> | ||
* [[Equipment Flags#EQ_PERIODIC|EQ_PERIODIC]] | * [[Equipment Flags#EQ_PERIODIC|EQ_PERIODIC]] | ||
Line 66: | Line 97: | ||
</div> | </div> | ||
===Source=== | |||
This field (i.e. the interrupt or event source) is only used if the equipment [[#Type|Type]] is set to [[Equipment Flags#EQ_INTERRUPT|EQ_INTERRUPT]] or [[Equipment Flags#EQ_MULTITHREAD|EQ_MULTITHREAD]]. The interrupt Source field is a bit-wise pattern representing the interrupt that is allowed to trigger the call to the [[readout routine]]. The @ref FE_poll_or_interrupt_readout_routine "example" shows a CAMAC or VME source for the interrupt. A MACRO (LAM_SOURCE) calculates the bit pattern from the parameters (Crate,Slot). | |||
If not using an interrupt, this field is set to 1. | If not using an interrupt, this field is set to 1. | ||
===Format=== | |||
Specifies the data format used for generating the event. Only [[Event Structure#MIDAS Format Event|"MIDAS"]] and [[Event Structure#FIXED Format Event|"FIXED"]] formats are valid in the frontend. The format must agree with the way the event is composed in the equipment [[readout routine]]. It tells the system how to interpret an event when it is copied to the ODB or displayed in a user-readable form. Data in MIDAS and/or FIXED format from the frontend can be saved by the MIDAS data logger [[Mlogger|mlogger]] in a number of formats (see [[Keys in the ODB /Logger/Channels tree #/Logger/Channels/0/Settings/Format | mlogger format]] ). | |||
'''NOTE''' | '''NOTE''' | ||
*MIDAS or FIXED data format can be mixed at the frontend level, but <span style="color:darkcyan;">''mlogger''</span> is not able to handle this format diversity on a event-by-event basis. | *MIDAS or FIXED data format can be mixed at the frontend level, but <span style="color:darkcyan;">''mlogger''</span> is not able to handle this format diversity on a event-by-event basis. | ||
In practice | : In practice, the data format (MIDAS/FIXED) should be identical throughout one equipment definition. Different equipments can, of course, have different formats in the same frontend. | ||
* ROOT format cannot be specified in the equipment definition. To save raw data in ROOT format, the [[#Bank definition]] must be supplied, and a conversion to ROOT format is done by the [[Keys in the ODB /Logger/Channels tree #/Logger/Channels/0/Settings/Format | data logger]] ). | |||
* ROOT format cannot be specified in the equipment definition. To save raw data in ROOT format, the [[#Bank definition]] must be supplied, and a conversion to ROOT | |||
format is done by the [[Keys in the ODB /Logger/Channels tree #/Logger/Channels/0/Settings/Format | data logger]] ). | |||
* For FIXED events, the [[Bank definition]] parameter may contain the [[Init String]]. | * For FIXED events, the [[Bank definition]] parameter may contain the [[Init String]]. | ||
===Enabled=== | |||
Enable switch for the equipment. Only when enabled (i.e. TRUE) is this equipment active. | |||
===ReadOn=== | |||
Specifies when the read-out of an event occurs or is enabled (i.e. on which transition state(s) and/or on which run state(s) respectively) by using a combination of | |||
[[ReadOn Flags]]. | |||
<div style="column-count:5;-moz-column-count:5;-webkit-column-count:5"> | |||
* [[ReadOn Flags|RO_RUNNING]] | |||
* [[ReadOn Flags|RO_STOPPED ]] | |||
* [[ReadOn Flags|RO_PAUSED ]] | |||
* [[ReadOn Flags|RO_BOR ]] | |||
* [[ReadOn Flags|RO_EOR]] | |||
* [[ReadOn Flags|RO_PAUSE]] | |||
* [[ReadOn Flags|RO_RESUME ]] | |||
* [[ReadOn Flags|RO_TRANSITIONS]] | |||
* [[ReadOn Flags|RO_ALWAYS ]] | |||
* RO_ODB | |||
</div> | |||
;NOTE : These flags can be combined with the logical OR operator,e.g. RO_RUNNING | RO_TRANSITIONS means that the event is read out when | |||
running and additionally on all transitions. | |||
===Period=== | |||
Time interval for [[Equipment Flags#EQ_PERIODIC|EQ_PERIODIC]] equipment or time out value in the case of [[Equipment Flags#EQ_POLLED|EQ_POLLED]] or [[Equipment Flags#EQ_MULTITHREAD|EQ_MULTITHREAD]] equipments (units are milliseconds). | |||
===Event limit=== | |||
Specifies the number of events to be taken prior to forcing an End-of-Run [[Run States and Transitions#transition]]. The value 0 disables this option. | |||
| | ===Number of subevents=== | ||
Enables the [[Super Event]] capability if > 0 . Specifies the maximum number of sub-events in the [[Super Event]]. (Not applicable to | |||
[[Event Structure#FIXED Format Event|FIXED format]] events.) |
Revision as of 16:01, 30 October 2013
Explanation of Equipment List Parameters
Links Equipment Declaration
#Equipment Name #EventID #TriggerMask #Equipment Type #Test1 #Buffer
#Equipment Type EQ_PERIODIC EQ_POLLED Q_INTERRUPT Q_MULTITHREAD EQ_SLOW EQ_MANUAL_TRIG EQ_EB EQ_FRAGMENTED
Introduction
The Equipment declaration in the frontend uses the EQUIPMENT structure defined in midas.h in the MIDAS package. Only those fields that are needed by the frontend are included (see example below). Some of these parameters are copied to the ODB /Equipment/<equipment-name>/Common subdirectory when the frontend is initialized.
Each of the parameters found in the frontend Equipment Declaration are described below.
Example Equipment declaration in a frontend
An example of an Equipment declaration in a frontend is shown below:
/*-- Equipment list ------------------------------------------------*/
EQUIPMENT equipment[] = {
{"Trigger", /* equipment name */ {1, 0, /* event ID, trigger mask */ "SYSTEM", /* event buffer */ EQ_POLLED, /* equipment type */ LAM_SOURCE(0, 0xFFFFFF), /* event source crate 0, all stations */ "MIDAS", /* format */ TRUE, /* enabled */ RO_RUNNING | /* read only when running */ RO_ODB, /* and update ODB */ 100, /* poll for 100ms */ 0, /* stop run after this event limit */ 0, /* number of sub events */ 0, /* don't log history */ "", "", "",}, read_trigger_event, /* readout routine */ },
{"Scaler", /* equipment name */ {2, 0, /* event ID, trigger mask */ "SYSTEM", /* event buffer */ EQ_PERIODIC | EQ_MANUAL_TRIG, /* equipment type */ 0, /* event source */ "MIDAS", /* format */ TRUE, /* enabled */ RO_RUNNING | RO_TRANSITIONS | /* read when running and on transitions */ RO_ODB, /* and update ODB */ 10000, /* read every 10 sec */ 0, /* stop run after this event limit */ 0, /* number of sub events */ 0, /* log history */ "", "", "",}, read_scaler_event, /* readout routine */ },
{""} };
EQUIPMENT Structure parameters
Equipment Name
Each equipment has to be assigned a unique Name. The name will be the reference name of the equipment generating the event. Examples of typical equipment Names are "Trigger","Scaler","Epics".
EventID
Each equipment has to be associated with a unique event ID . The event ID will be part of the event header of that particular equipment.
TriggerMask
If the equipment Type is EQ_INTERRUPT or EQ_MULTITHREAD, each equipment must be associated with a unique Trigger Mask In this case, the Trigger Mask can be modified dynamically by the readout routine to define a subevent type on an event-by-event basis. This can be used to mix "physics events" (from a physics trigger) and "calibration events" (from a clock for example) in one run and identify them later. Both parameters are declared as 16-bit values. If the Trigger Mask is used in a single bit-wise mode, 16 is the maximum number of different masks available.
Buffer
Specifies the name of the Buffer to which the event will be sent. After composition of an equipment, the Midas Frontend mfe.c takes over the sending of this event to the buffer (usually the SYSTEM buffer) on the back-end computer where it may be sent to the data logger [([mlogger]]) and the analyser.
- If this field is left empty, (i.e. set to ""), the readout function associated with that equipment will still be performed, but the actual event won't be sent to the buffer. Instead, that particular equipment can be mirrored in the ODB if the RO_ODB flag is turned on (see @ref FE_RO_ODB_example "example"). The ODB is updated with a new event approximately every second. Note that this feature is generally used only for testing or monitoring, as writing large amounts of data to the ODB takes time.
- By using a buffer other than the SYSTEM buffer, Event Filtering can be implemented.
- If using an Event Builder ( i.e. a secondary stage on the back-end to collect and assemble events coming from different buffers in order to compose a larger event) , a dedicated buffer can be specified. In this case the EQ_EB flag must be turned on, and the events coming from the Frontend are called fragments.
Type
Type specifies the type of equipment, and should be set to one of the Equipment Flags EQ_XXX selected from the list of valid Equipment Flags, i.e. one of
Source
This field (i.e. the interrupt or event source) is only used if the equipment Type is set to EQ_INTERRUPT or EQ_MULTITHREAD. The interrupt Source field is a bit-wise pattern representing the interrupt that is allowed to trigger the call to the readout routine. The @ref FE_poll_or_interrupt_readout_routine "example" shows a CAMAC or VME source for the interrupt. A MACRO (LAM_SOURCE) calculates the bit pattern from the parameters (Crate,Slot).
If not using an interrupt, this field is set to 1.
Format
Specifies the data format used for generating the event. Only "MIDAS" and "FIXED" formats are valid in the frontend. The format must agree with the way the event is composed in the equipment readout routine. It tells the system how to interpret an event when it is copied to the ODB or displayed in a user-readable form. Data in MIDAS and/or FIXED format from the frontend can be saved by the MIDAS data logger mlogger in a number of formats (see mlogger format ). NOTE
- MIDAS or FIXED data format can be mixed at the frontend level, but mlogger is not able to handle this format diversity on a event-by-event basis.
- In practice, the data format (MIDAS/FIXED) should be identical throughout one equipment definition. Different equipments can, of course, have different formats in the same frontend.
- ROOT format cannot be specified in the equipment definition. To save raw data in ROOT format, the #Bank definition must be supplied, and a conversion to ROOT format is done by the data logger ).
- For FIXED events, the Bank definition parameter may contain the Init String.
Enabled
Enable switch for the equipment. Only when enabled (i.e. TRUE) is this equipment active.
ReadOn
Specifies when the read-out of an event occurs or is enabled (i.e. on which transition state(s) and/or on which run state(s) respectively) by using a combination of ReadOn Flags.
- NOTE
- These flags can be combined with the logical OR operator,e.g. RO_RUNNING | RO_TRANSITIONS means that the event is read out when
running and additionally on all transitions.
Period
Time interval for EQ_PERIODIC equipment or time out value in the case of EQ_POLLED or EQ_MULTITHREAD equipments (units are milliseconds).
Event limit
Specifies the number of events to be taken prior to forcing an End-of-Run Run States and Transitions#transition. The value 0 disables this option.
Number of subevents
Enables the Super Event capability if > 0 . Specifies the maximum number of sub-events in the Super Event. (Not applicable to FIXED format events.)