Entry  16 May 2024, Konstantin Olchanski, Bug Report, midas alarm borked condition evaluation 
    Reply  17 May 2024, Stefan Ritt, Bug Report, midas alarm borked condition evaluation 
       Reply  17 May 2024, Konstantin Olchanski, Bug Report, midas alarm borked condition evaluation 
          Reply  17 May 2024, Konstantin Olchanski, Bug Report, midas alarm borked condition evaluation 
             Reply  18 May 2024, Stefan Ritt, Bug Report, midas alarm borked condition evaluation MSetPoint.png
Message ID: 2767     Entry time: 16 May 2024     Reply to this: 2768
Author: Konstantin Olchanski 
Topic: Bug Report 
Subject: midas alarm borked condition evaluation 
I am updating the TRIUMF IRIS experiment to the latest version of MIDAS. I see following error messages in midas.log:

19:06:16.806 2024/05/16 [mhttpd,ERROR] [odb.cxx:6967:db_get_data_index,ERROR] index (29) exceeds array length (20) for key 
"/Equipment/Beamline/Variables/Measured"

19:06:15.806 2024/05/16 [mhttpd,ERROR] [odb.cxx:6967:db_get_data_index,ERROR] index (30) exceeds array length (20) for key 
"/Equipment/Beamline/Variables/Measured"

The errors are correct, there is only 20 elements in that array. The errors are coming every few seconds, they spam midas.log. How do I fix 
them? Where do they come from? There is no additional diagnostics or information to go from.

In the worst case, they come from some custom web page that reads wrong index variables from ODB. mhttpd currently provides no diagnostics to 
find out which web page could be causing this.

But maybe it's internal to MIDAS? I save odb to odb.json, "grep Measured odb.json" yields:
iris00:~> grep Measured odb.json 
        "Condition" : "/Equipment/Beamline/Variables/Measured[29] > 1e-5",
        "Condition" : "/Equipment/Beamline/Variables/Measured[30] < 0.5",

So wrong index errors is coming from evaluated alarms.
ODB "/Alarms/Alarm system active" is set to "no" (alarm system is disabled), the errors are coming.
ODB "/Alarms/Alarms/TP4/Active" is set to "no" (specific alarm is disabled), the errors are coming.
WTF? (and this is recentish borkage, old IRIS MIDAS had the same wrong index alarms and did not generate these errors).

Breakage:
- where is the error message "evaluated alarm XXX cannot be computed because YYY cannot be read from ODB!"
- disabled alarm should not be computed
- alarm system is disabled, alarms should not be computed

K.O.

P.S. I am filing bug reports here, I cannot be bothered with the 25-factor authentication to access bitbucket.