Entry  16 May 2024, Konstantin Olchanski, Bug Report, midas alarm borked condition evaluation 
    Reply  17 May 2024, Stefan Ritt, Bug Report, midas alarm borked condition evaluation 
       Reply  17 May 2024, Konstantin Olchanski, Bug Report, midas alarm borked condition evaluation 
          Reply  17 May 2024, Konstantin Olchanski, Bug Report, midas alarm borked condition evaluation 
             Reply  18 May 2024, Stefan Ritt, Bug Report, midas alarm borked condition evaluation MSetPoint.png
Message ID: 2769     Entry time: 17 May 2024     In reply to: 2768     Reply to this: 2771
Author: Konstantin Olchanski 
Topic: Bug Report 
Subject: midas alarm borked condition evaluation 
> This is a common problem I also encountered in the past. You get a low-level ODB access error (could also be a read of a non-existing key) and you 
> have no idea where this comes from. Could be the alarm system, a mhttpd web page, even some user code in a front-end over which the midas library 
> has no control.

committed a partial fix, added an error message in alarm condition evaluation code to report alarm name and odb paths when we cannot get something from 
ODB. Now at least midas.log gives some clue that ODB errors are coming from alarms.

and the errors are actually coming from the alarms web page.

the alarms web page shows all the alarms even if alarms are disabled and it shows evaluated alarm conditions and current values even for alarms that 
are disabled.

I could change it to show "disabled" for disabled alarms, but I think it would not be an improvement,
right now it is quite convenient to see the alarm values for disabled/inactive alarms,
it is easy to see if they will immediately trip if I enable them. Hiding the values would make
them blind.

And I think I know what caused the original problem in IRIS experiment, I think the list of EPICS variables got truncated from 30 to 20 and EPICS 
values 29 and 30 used in the alarm conditions have become lost.

So the next step is to fix feepics to not truncate the list of variables (right now it is hardwired to 20 variables) and restore
the lost variable definition from a saved odb dump.

K.O.






> 
> One option would be to add a complete stack dump to each of these error (ROOT does something like that), but I hear already people shouting "my 
> midas.log is flooded with stack dumps!". So what I do in this case is I run a midas program in the debugger and set a breakpoint (in your case at 
> odb.cxx:6967). If the breakpoint triggers, I inspect the stack and find out where this comes from.
> 
> Not that I print a stack dump for such error in the odbxx API. This goes to stdout, not the midas log, and it helped me in the past. Unfortunately 
> stack dumps work only under linux (not MacOSX), and they do not contain all information a debugger can show you.
> 
> It is not true that alarm conditions are evaluated when the alarm system is off. I just tried and it works fine. The code is here:
> 
> alarm.cxx:591
> 
>       /* check global alarm flag */
>       flag = TRUE;
>       size = sizeof(flag);
>       db_get_value(hDB, 0, "/Alarms/Alarm system active", &flag, &size, TID_BOOL, TRUE);
>       if (!flag)
>          return AL_SUCCESS;
> 
> so no idea why you see this error if you correctly st "Alarm system active" to false.
> 
> Stefan