Revision as of 12:38, 5 May 2022
Links
POL Main Status Page
Run Stopped
Point a browser to https://isdaq01:8445/ to access the POL experiment Main Status page (Figure 2). In this example, the run is stopped and the status of the POL Equipments POL_ACQ,VME,INFO,HISTO are coloured green. This indicates that the frontend program (which defines these software Equipments) is running.
If the frontend program is not running, they will be shown as orange. Clicking on these links (POL_ACQ,VME,INFO,HISTO) will show the last event data for those equipments that send the data to the ODB. See also [[vmicbanks.html">Data Banks output by the POL frontend]].
Figure 2 also shows the Alarm System is OFF, and data logging disabled.
- Figure 2 Experiment pol main status page when run is stopped
Figure 2: Pol experiment main status page
The top line of buttons (Figure 2) i.e. Start/ODB/Messages/Programs etc) are standard MIDAS buttons. The Start button can be used to start the run, the other buttons give access to other pages (e.g. Messages, Programs Alarms etc.). The ODB button allows access to the ODB (online data base) in which all the run parameters are stored.
Note that various "user buttons" have been defined for POL experiment. These buttons appear on the main status page as the second row of buttons below the row of standard Midas buttons. All are Alias or Custom Buttons. The alias buttons are short-cuts to display specific parts of the ODB. Custom buttons switch to a custom page.
- ppg blocks - alias button accesses the blocks that define the ppg cycle
- sis - alias button accesses the SIS3820 MCS ODB parameters
- input - alias button accesses the complete list of ODB input parameters
- output - alias button accesses the ODB output parameters
- ppg_cycle - custom button accesses the POL Custom page
Run in Progress
When a run is in progress, the Main status page appears as in Figure 3. In this case, the #Alarm_System">alarm system is enabled, #Logging_the_data">data logging in enabled, and the Equipment Events column shows that a number of INFO and HISTO events have been sent by the frontend.
- Figure 3 Main status page when run is in progress
Figure 3:main status page with run in progress
The ppg_cycle custom button will be most commonly used, since it gives access to the #Pol Custom page.
Display INFO Data Banks
Because the INFO Equipment sends its data banks to the ODB, the contents of these banks can be displayed from the main Status page by clicking on the INFO link, e.g.
Figure 4 Contents of INFO Data Banks
Figure 4: Display of INFO banks from status page
Programs page
The programs page is obtained by clicking on the Programs button on the main status (or custom) page. If the frontend is running, the page will appear as in Figure 5.
- Figure 5 Programs page showing frontend is running
Figure 5: Programs page showing frontend running
You can stop the frontend program by clicking the button "Stop pol_fevme". The page will then look like Figure 6. Clicking on "Start pol_fevme" will restart the frontend in its xterm.
- Figure 6 Programs page showing frontend is stopped
Figure 6: Programs page showing frontend stopped
Pol Custom page
A custom page for POL has been provided to make it easier for the experimenters to enter the relevent input parameters.
To access the POL Custom page from the #POL Main Status Page, click on the custom button "ppg cycle".
The custom page is shown in Figure 7. This includes graphic
representations of one DAC scan, one SuperCycle and one
PPG cycle, plus a table of input
parameters for the experiment. The values of some of the parameters
are shown as labels on the graphic.
The Run Status is also shown (Stopped) and the Frontend status shows that the frontend program
pol_fevme.exe is running. The frontend status graphic can be slow to change colour after the page is reloaded, since it is accessing a watchdog which is rarely updated.
A smaller #Information_Box">information table is also shown.
Buttons are provided to start a run, to access other standard MIDAS pages. Pressing Doc will display this page.
Enter the Input Parameters
The current input parameter values appear on the #Pol Custom Page in the box titled "Input Parameters". To change the input parameter values, click on the hyperlinks and enter the new values. If an illegal value is input, an alert box will appear.
An explanation of each parameter is shown below (#List of Input Parameters").
List of Input Parameters
There are a number of parameters in the ODB that control the experiment. The ones most relevent to the experimenters are listed below. These appear in the Input Parameters box on the custom page.
- number of time bins
- together with "Dwell time", determines length of PPG cycle
- Dwell time (ms)
- together with "number of time bins", determines length of PPG cycle
- DAC start(Volts)
- Voltage at which #DAC_scan should start
- DAC increment (Volts)
- Voltage to increment DAC each step
- Number of DAC increments
- Number of increments for DAC scan
- DAC sleep time (ms)
- Time to delay after changing DAC. Always set to zero. May be removed from the parameter table.
- TOF pulse width (ms)
- Width of "Start TOF" pulse width. Always set to zero (i.e. minimum width). May be removed from the parameter table.
- Number of PPG cycles per #supercycle
- Number of PPG cycles for which data is to be summed at each DAC step
- Number of scans
- run will stop automatically after this number of scans, or enter 0 for free-running
- Figure 7 POL Custom page showing the table of input parameters when the run is stopped.
Figure 7: Pol Custom page showing the table of input parameters with the run stopped
Frontend Flags
Several frontend flags (also in the ODB) are shown on the #Pol Custom Page. See Hardware for more information.
- discard first bin of every PPG cycle
- first bin will contain spurious data collected during the TOF. Always set this to "y" (discard) unless
in test mode.
- discard first PPG cycle of every SuperCycle
- first PPG cycle is started by software, and will contain spurious data. Always set this to "y" (discard) unless in test mode.
- PPG external start
- Always set to "y" when running the experiment. The PPG external start signal is supplied at the end of the TOF. This may be set to "n" for testing when an external signal is not available.
- Toggle Hot Debug*
- set to "n" unless debugging. This causes extra debugging information to be printed by the frontend. It will also slow down the data acquisition slightly.
- Toggle Hot Timer*
- set to "n" unless debugging. This causes extra timing information to be printed by the frontend. It will also slow down the data acquisition slightly.
*This is a "hot link", which means that it takes effect immediately, instead of only being read at the beginning of run.
Information Table
An extra information table (Table 1) has also been provided on the Custom Page (Figure 7 ) containing parameters that do not need to be changed very often. This includes a link to enable/disable the #Alarm_System.
Table 1a: DAC checks enabled | Table 1b: DAC checks disabled |
File:Pol info tbl.png | File:Pol info tbl noDACchk.png |
Other contents are links to parameters used when stepping the Galil RIO DAC voltage. Unless disabled (Table 1b), a check is done to verify that the DAC voltage has changed each time the DAC has stepped (see algorithm).
These are used to help determine that the DAC voltage has incremented when the increment value is very small. Once determined, they should be left as constants.
- Disable DAC check
- This should normally be set FALSE. When enabled, a check is done to verify that the DAC voltage has changed after the DAC has stepped.
- DAC minimum increment (V)
- This is set to a suitable value larger than the "jitter".
- DAC jitter (V)
- This is set to a suitable value larger than the LSB. It represents the variation you might get when reading the same DAC value several times.
Start a run
Start a run either from the #Pol Custom page (or the #POL_Main_Status_Page">Main Status page) by clicking on the "Start" button. A window as in Figure 8 will then appear. This is the Start Page, and shows the edit-on-start parameters.
Except for testing, the Write data parameter should be checked as shown, so that data is stored on disk. The other parameter controls sending the raw data bank (see ... ) and should not be checked unless debugging.
- Figure 8 Run Start window showing edit-on-start parameters
Logging the data
If data is to be logged, check the "write data" box on the run start page (Figure 8 above). The data will be saved in the directory given by the ODB key /logger/Data dir.
When logging is enabled, the data directory is also shown on the Main Status page Figure 3.
Custom Page with Run in Progress
- If the run is started from the Main Status page
the Main Status page will reappear as in Figure 3. Event statistics (e.g. the number of each event type output, the event rates etc.) can be seen on this page.
- If the run is started from the POL Custom page
after the screen is reloaded, the Custom Page will appear as Figure 9, with the Input Parameter table replaced by the front-end statistics table which
shows the progress of the run.
- Figure 9 Pol Custom page with the run in progress.
Parameters Table
The values shown in the Parameters Table are described below:
Parameters | |||||
Per PPG Cycle | Per Supercycle | ||||
Bins | True number of bins per PPG Cycle. This will be the #number of time bins requested + 1 if parameter #discard first bin of every PPG cycle is true).
This is the number of bins you would see looking at PPG output MSC Next on the oscilloscope. |
Cycles | True number of PPGcycles per supercycle.This will be the (#number of cycles per supercycle requested + 1) if parameter #discard first cycle of every SuperCycle is true)
This is the number of bins you would see looking at PPG output MSC Next on the oscilloscope over a SuperCycle. |
Totbins | True total number of bins in one SuperCycle
This will be the number requested + any bins discarded |
Discard | This will be 1 if parameter discard first bin of every PPG cycle is true, otherwise 0 | Discard | This will be 1 if parameter discard first
bin of every SuperCycle is true, otherwise 0 |
Discard | The number of bins discarded
or 0 if none have been discarded.
|
Bins | The number of bins requested by the user, and also the number of data bins in the
histograms. |
Cycles | The number of cycles/supercycle requested by the user. | Totbins | The number of bins in one SuperCycle requested by the user. |
Frontend Statistics Table
The contents of the frontend statistics table are described below. The statistics table is not updated very often. The statistics data are sent to the ODB at the end of each supercycle, but the custom page is updated every 5s or so. Some of these counters are used to check the frontend is running correctly (this is more for debugging).
Counter | Explanation |
Cycle | counts #cycles. It will count up in units of Cycles/Supercycle |
SCycle | counts supercycles. |
DAC Scans | counts the number of complete #DAC_scan"s |
DAC Inc | shows the current increment number within the DAC scan. Varies from 1 to #number of DAC increments |
DAC Set(V) | shows the current setting of the DAC in volts |
Buffrd | the number of data words still buffered in the SIS3820 - usually 0 for small (<4K) events where buffer can be read in one operation. |
LNE/cyc | #True number of time bins (i.e. LNE events) read out from the SIS3820 scaler per PPG cycle. Should be the same as counter Nbins. |
LNEfromSIS | LNE count read out from SIS3820 acquisition count register (i.e. number of input LNE
pulses device has received from PPG output). |
LNEpreset | LNE preset value set in the SIS3820 preset register. Should be the same as #True Total Number of bins/supercycle. |
Nbins | True number of time bins per cycle. |
Sum per SuperCycle | Sum of all the time bins for each Input Channel of the scaler over 1 SuperCycle |
- Note
- in normal operation, the counters
- LNE/cyc and Nbins will both be equal to #True number of bins/cycle
- LNEfromSIS and LNEpreset will both be equal to #True total number of bins/SuperCycle.
Stop the run
To stop the run, press Stop. You will see a "transition in progress" state while the run is stopping.
Pressing Stop will stop the run mid-cycle. To stop the run at the end of the present DAC scan, use StopAtEndScan on the Custom page.
Run stops automatically
The run will stop automatically if
- a fatal error is detected
or
- if the input parameter num DAC scans before run stops is > 0, and that number of scans has been reached
Alarm System
MIDAS provides an alarm system which can be used to indicate various problems to the user.
- Note
- the alarm system should always be enabled unless testing.
Enabling/disabling the alarm system can be done using the Information Table on the #Pol Custom page (Table 4a), or by pressing Alarm on either the Custom or main status page.
If the alarm system is disabled, the alarm system line on the Information Table on the custom page (Table 4b) will turn red.
Table 4a: ... with alarm enabled | Table 4b: ... with alarm disabled |
---|---|
info table with alarm enabled | information table with alarms disabled" |
Figure 10 shows an alarm status banner on the main status
page. A similar banner will appear on the Custom page.
- Figure 10 Main status page showing alarm banner
The alarm banner will disappear if Alarm
Reset is pressed.
However, it will reappear after a short time if the alarm condition is not fixed.
Error/Information Messages
MIDAS has a sophisticated messaging scheme, whereby messages from the various clients are collected together in the message buffer. This can be easily viewed by pressing Messages at the top of the #POL Main Status Page or #Pol Custom page.
The most recent error/information message is displayed at the bottom of the Main Status page and the POL Custom Page.
Additional messages from the frontend code can be viewed in the #The Frontend window for the POL experiment.