Back Midas Rome Roody Rootana
  Midas DAQ System  Not logged in ELOG logo
Entry  10 Aug 2020, Ivo Schulthess, Bug Report, data missing in runXXXXXX.mid 
    Reply  10 Aug 2020, Stefan Ritt, Bug Report, data missing in runXXXXXX.mid 
       Reply  10 Aug 2020, Ivo Schulthess, Bug Report, data missing in runXXXXXX.mid 
          Reply  10 Aug 2020, Stefan Ritt, Bug Report, data missing in runXXXXXX.mid 
             Reply  10 Aug 2020, Ivo Schulthess, Bug Report, data missing in runXXXXXX.mid 
                Reply  10 Aug 2020, Stefan Ritt, Bug Report, data missing in runXXXXXX.mid 
                   Reply  10 Aug 2020, Ivo Schulthess, Bug Report, data missing in runXXXXXX.mid 
                      Reply  10 Aug 2020, Stefan Ritt, Bug Report, data missing in runXXXXXX.mid 
                         Reply  10 Aug 2020, Ivo Schulthess, Bug Report, data missing in runXXXXXX.mid 
                            Reply  10 Aug 2020, Stefan Ritt, Bug Report, data missing in runXXXXXX.mid 
                               Reply  11 Aug 2020, Konstantin Olchanski, Bug Report, data missing in runXXXXXX.mid 
                                  Reply  11 Aug 2020, Ivo Schulthess, Bug Report, data missing in runXXXXXX.mid 
                                     Reply  24 Mar 2022, Konstantin Olchanski, Bug Report, data missing in runXXXXXX.mid 
                                        Reply  24 Mar 2022, Stefan Ritt, Bug Report, data missing in runXXXXXX.mid 
                                           Reply  24 Mar 2022, Konstantin Olchanski, Bug Report, data missing in runXXXXXX.mid 
This is a draft message, edit and submit it to make it permanent  
Message ID: 1977     Entry time: 10 Aug 2020     In reply to: 1973
Author: Pierre-Andre Amaudruz 
Topic: Bug Report 
Subject: data missing in runXXXXXX.mid 
> Have you tried longer files? Maybe a few 100 MB or so. Maybe a buffer is not flushed correctly at the end of a run.

Hi,

If the online mdump is correct (by default using the -1, -1 filter), the data are in the main SYSTEM buffer. 

by the way, similar to the dump - mdump -x file.mid -m raw -d x will show you the events.

The fact that the analyzer doesn't see the banks would indicate a buffer handling issue as mentioned by Stefan.
To confirm, I would check at the end of a run that the sum of the equipment "events sent" matches the logger "Events written".
ELOG V3.1.4-2e1708b5