Back Midas Rome Roody Rootana
  Midas DAQ System, Page 141 of 157  Not logged in ELOG logo
    Reply  18 Oct 2024, Konstantin Olchanski, Bug Report, Difficulty running MIDAS on Rocky 9.4 
> suddenly, an ODB semaphore timeout...

I am wondering if something bizarre is going on, like the system clock going backwards. I heard of things like that 
happening in virtual environments.

https://stackoverflow.com/questions/4801122/how-to-stop-time-from-running-backwards-on-linux

I added some debugging information to the semaphore locking code. Please update to commit 
eb625af119067f6d702211542d88a28ccb57ad2c of src/system.cxx (plus small change in include/msystem.h) and try again.

Now for each timeout it will print detailed syscall and timing information, if time goes backwards, it should catch it.

K.O.
    Reply  28 Oct 2024, Amy Roberts, Bug Report, Difficulty running MIDAS on Rocky 9.4 
> Now for each timeout it will print detailed syscall and timing information, if time goes backwards, it should catch it.

It appears that time is moving forward:

[aroberts@sdfcdmsdaq build]$ odbedit
[ODBEdit,ERROR] [odb.cxx:2043:db_open_database,ERROR] Removed ODB client 'ODBEdit', index 0 because process pid 1617119 does 
not exists
[ODBEdit,INFO] Removed open record flag from "/Experiment/Security/RPC hosts/Allowed hosts"
[ODBEdit,INFO] Removed exclusive access mode from "/Experiment/Security/RPC hosts/Allowed hosts"
[ODBEdit,INFO] Corrected 1 ODB entries
[ODBEdit,INFO] Deleted entry '/System/Clients/1617119' for client 'ODBEdit' because it is not connected to ODB
[ODBEdit,INFO] Client 'ODBEdit' on buffer 'SYSMSG' removed by bm_open_buffer because process pid 1617119 does not exist
[local:amy_test:S]/>ss_semaphore_wait_for: semop/semtimedop(5) returned -1, errno 11 (Resource temporarily unavailable), 
start time 0xd4fd98f6, now 0xd4fdc0ef, dt 0x000027f9, timeout 0x00002710 ms, SEMAPHORE TIMEOUT!
[ODBEdit,ERROR] [odb.cxx:2489:db_lock_database,ERROR] cannot lock ODB semaphore, timeout 10000 ms, aborting...
Aborted (core dumped)
    Reply  06 Nov 2024, Amy Roberts, Bug Report, Difficulty running MIDAS on Rocky 9.4 
After following Konstantin's debugging suggestions, I thought I would try to replicate 
the issue on my own computer.  My hope was that I could provide instructions for 
replicating the bug so that the MIDAS team could try debugging things more easily.

However, when I ran the current version of MIDAS in a Rocky 9.4 VM on my laptop (both 
VMWare and VirtualBox), mserver and odbedit ran just fine (!).

I'm currently trying to find out if there's a way to compare the VMs on my machine and 
the machine that's being problematic, I'll report back if I learn anything.
Entry  12 Feb 2020, Marius Koeppel, Forum, Difference between "Event Data Size" and "All Bank Size" 
Dear all,

we are trying to build Midas events on FPGAs and send them directly to the midas
ring buffer via copy_n. According to the wiki
https://midas.triumf.ca/MidasWiki/index.php/Event_Structure Event Data Size is:
"The event data size contains the size of the event in bytes excluding the
header." and All Bank Size is: "Size in bytes of the following data plus the
size of the bank header". So are they actually the same or what header is the
header in the first sentence also the bank header?

Cheers,
Marius

 
    Reply  12 Feb 2020, Stefan Ritt, Forum, Difference between "Event Data Size" and "All Bank Size" 
Thanks for pointing out this error. The "All Bank Size" contains the size of all banks including their 
bank headers, but NOT the global bank header itself. I modified the documentation accordingly.

If you want to study the C code which tells you how to fill these headers, look at midas.cxx line 
14788.

Best,
Stefan

> Dear all,
> 
> we are trying to build Midas events on FPGAs and send them directly to the midas
> ring buffer via copy_n. According to the wiki
> https://midas.triumf.ca/MidasWiki/index.php/Event_Structure Event Data Size is:
> "The event data size contains the size of the event in bytes excluding the
> header." and All Bank Size is: "Size in bytes of the following data plus the
> size of the bank header". So are they actually the same or what header is the
> header in the first sentence also the bank header?
> 
> Cheers,
> Marius
> 
>  
    Reply  20 Feb 2020, Konstantin Olchanski, Forum, Difference between "Event Data Size" and "All Bank Size" 
> Thanks for pointing out this error. The "All Bank Size" contains the size of all banks including their 
> bank headers, but NOT the global bank header itself. I modified the documentation accordingly.
> 
> If you want to study the C code which tells you how to fill these headers, look at midas.cxx line 
> 14788.

Also take a look at the midas event parser in ROOTANA midasio.cxx, the code is pretty clean c++
https://bitbucket.org/tmidas/rootana/src/master/libMidasInterface/midasio.cxx

But Stefan's code in midas.cxx and in the documentation is the authoritative information.

K.O.
Entry  23 Oct 2023, Francesco Renga, Forum, Device with inputs and outputs 
Dear all,
       I'm writing a very simple device driver starting from the nulldev.cxx 
example. 

I define an equipment as reported at the end of this message then, if all 
variables are Input variables, I define them with:

  mdevice device("myEquimpent", "Input", DF_INPUT | DF_MULTITHREAD, mydevice);
  device.define_var("Var1", 0.1);
  device.define_var("Var2", 0.1);
  ...

If all variables are output variables, I define them with:

  mdevice device("myEquipment", "Output", DF_OUTPUT | DF_MULTITHREAD, mydevice);
  device.define_var("Var1", 0.1);
  device.define_var("Var2", 0.1);

But I don't know what to do if I have mixed input and output variables in the same 
device. I think I can do:

  mdevice device_in("myEquipment", "Input", DF_INPUT | DF_MULTITHREAD, mydevice);
  device.define_var("Var1", 0.1);

  mdevice device_out("myEquipment", "Output", DF_OUTPUT | DF_MULTITHREAD, 
mydevice);
  device.define_var("Var2", 0.1);

but in this case, inside mydevice.cxx, I don't know how to distinguish Var1 and 
Var2, because they are both identified as channel 0.

Do you have any suggestion?

Thank you,
      Francesco




-------------------------------------------------------------------



   {"SourceMotor",                       /* equipment name */
    {7, 0,                       /* event ID, trigger mask */
     "SYSTEM",                  /* event buffer */
     EQ_SLOW,                   /* equipment type */
     0,                         /* event source */
     "MIDAS",                   /* format */
     TRUE,                      /* enabled */
     RO_ALWAYS,        /* read when running and on transitions */
     60000,                     /* read every 60 sec */
     0,                         /* stop run after this event limit */
     0,                         /* number of sub events */
     1,                         /* log history every event */
     "", "", ""} ,
    cd_multi_read,                 /* readout routine */
    cd_multi,                      /* class driver main routine */
   },
    Reply  24 Oct 2023, Stefan Ritt, Forum, Device with inputs and outputs 
The "multi" class driver takes care of that. It properly calls the SET and GET functions 
with the correct index. The code for that is in multi.cxx:105:

 device_driver(m_info->driver_input[i], CMD_GET,
               i - m_info->channel_offset_input[i],
               &m_info->var_input[i]);

The "channel_offset_input" and "channel_offset_output" store the first index of the 
channel in the overall ODB array (where inputs and outputs are staggered together), so 
the device_driver is always called with an index 0...n each for input and output, but 
with different commands CMD_GET and CMD_SET. You can take the mscbdev.cxx device driver 
as a working example.

Stefan
Entry  16 Dec 2021, Zaher Salman, Forum, Device driver for modbus 
Dear all, does anyone have an example of for a device driver using modbus or modbus tcp to communicate with a device and willing to share it? Thanks.
    Reply  26 Jan 2022, Konstantin Olchanski, Forum, Device driver for modbus 
> Dear all, does anyone have an example of for a device driver using modbus or modbus tcp to communicate with a device and willing to share it? Thanks.

I have not seen any modbus devices recently, so all my code and examples are quite old.

Basic modbus/tcp communication driver is in the midas repo:

daq00:midas$ find . | grep -i modbus
./drivers/divers/ModbusTcp.cxx
./drivers/divers/ModbusTcp.h
daq00:midas$ 

This driver worked for communication to a modbus PLC (T2K/ND280/TPC experiment in Japan).

An example program to use this driver and test modbus communication is here:
https://bitbucket.org/expalpha/agdaq/src/master/src/modbus.cxx

Because at the end, we do not have any modbus devices in any recent experiment,
I do not have any example of using this driver in the midas frontend. Sorry.

K.O.
Entry  10 May 2023, Lukas Gerritzen, Suggestion, Desktop notifications for messages 
It would be nice to have MIDAS notifications pop up outside of the browser window.

To get enable this myself, I hijacked the speech synthesis and I added the following to mhttpd_speak_now(text) inside mhttpd.js:
let notification = new Notification('MIDAS Message', {
    body: text,
});

I couldn't ask for the permission for notifications here, as Firefox threw the error "The Notification permission may only be requested from inside a short running user-generated event handler". Therefore, I added a button to config.html:
<button class="mbutton" onclick="Notification.requestPermission()">Request notification permission</button>

There might be a more elegant solution to request the permission.
    Reply  10 May 2023, Stefan Ritt, Suggestion, Desktop notifications for messages 

Lukas Gerritzen wrote:
It would be nice to have MIDAS notifications pop up outside of the browser window.


There are certainly dozens of people who do "I don't like pop-up windows all the time". So this has to come with a switch in the config page to turn it off. If there is a switch "allow pop-up windows", then we have the other fraction of people using Edge/Chrome/Safari/Opera saying "it's not working on my specific browser on version x.y.z". So I'm only willing to add that feature if we are sure it's a standard things working in most environments.

Best,
Stefan
    Reply  10 May 2023, Lukas Gerritzen, Suggestion, Desktop notifications for messages 

Stefan Ritt wrote:

people using Edge/Chrome/Safari/Opera saying "it's not working on my specific browser on version x.y.z". So I'm only willing to add that feature if we are sure it's a standard things working in most environments.



[The API looks pretty standard to me. Firefox, Chrome, Opera have been supporting it for about 9 years, Safari for almost 6. I didn't find out when Edge 14 was released, but they're at version 112 now.

Since browsers don't want to annoy their users, many don't allow websites to ask for permissions without user interaction. So the workflow would be something like: The user has to press a button "please ask for permission", then the browser opens a dialog "do you want to grant this website permission to show notifications?" and only then it works. So I don't think it's an annoying popup-mess, especially since system notifications don't capture the focus and typically vanish after a few seconds. If that feature is hidden behind a button on the config page, it shouldn't lead to surprises. Especially since users can always revoke that permission.
    Reply  11 May 2023, Stefan Ritt, Suggestion, Desktop notifications for messages 
Ok, I implemented desktop notifications. In the MIDAS config page, you can now enable browser notifications for the different types of messages. Not sure this works perfectly, but a staring point. So please let me know if there is any issue.

Stefan
Entry  28 Aug 2018, Lukas Gerritzen, Bug Report, Deleting Links in ODB via mhttpd 
Asume you have a variable foo and a link bar -> foo. When you go to the ODB in
mhttpd, click "Delete" and select bar, it actually deletes foo. bar stays,
stating "<cannot resolve link>". Trying the same in odbedit with rm gives the
expected result (bar is gone, foo is still there).

I'm on the develop branch.
    Reply  28 Aug 2018, Konstantin Olchanski, Bug Report, Deleting Links in ODB via mhttpd 
> Asume you have a variable foo and a link bar -> foo. When you go to the ODB in
> mhttpd, click "Delete" and select bar, it actually deletes foo. bar stays,
> stating "<cannot resolve link>". Trying the same in odbedit with rm gives the
> expected result (bar is gone, foo is still there).
> 
> I'm on the develop branch.

I think I can confirm this. Created a bug report on bitbucket:

https://bitbucket.org/tmidas/midas/issues/148/mhttpd-odb-editor-deletes-wrong-symlink

K.O.
    Reply  29 Aug 2018, Stefan Ritt, Bug Report, Deleting Links in ODB via mhttpd 
> > Asume you have a variable foo and a link bar -> foo. When you go to the ODB in
> > mhttpd, click "Delete" and select bar, it actually deletes foo. bar stays,
> > stating "<cannot resolve link>". Trying the same in odbedit with rm gives the
> > expected result (bar is gone, foo is still there).
> > 
> > I'm on the develop branch.
> 
> I think I can confirm this. Created a bug report on bitbucket:
> 
> https://bitbucket.org/tmidas/midas/issues/148/mhttpd-odb-editor-deletes-wrong-symlink
> 
> K.O.

I fixed this and committed the change. Took me a while since it was in KO's code.

Stefan
Entry  06 Sep 2009, Exaos Lee, Bug Report, Delete key "/A_Str" problem odbedit.png
Another problem while using odbedit.
I tried the batch mode of "odbedit". I created a key as "/A_Str" by mistake and 
wanted to delete it. Then "odbedit" failed to accept the "Return" key. Please see 
the screen-shot attached. :-(
    Reply  06 Sep 2009, Exaos Lee, Bug Report, Delete key "/A_Str" problem 
> Another problem while using odbedit.
> I tried the batch mode of "odbedit". I created a key as "/A_Str" by mistake and 
> wanted to delete it. Then "odbedit" failed to accept the "Return" key. Please see 
> the screen-shot attached. :-(

This bug has been fixed in the latest repository.
I encountered it in svn-r4488.
Entry  19 Feb 2025, Lukas Gerritzen, Bug Report, Default write cache size for new equipments breaks compatibility with older equipments 
We have a frontend for slow control with a lot of legacy code. I wanted to add a new equipment using the
mdev_mscb class. It seems like the default write cache size is 1000000B now, which produces error
messages like this:
12:51:20.154 2025/02/19 [SC Frontend,ERROR] [mfe.cxx:620:register_equipment,ERROR] Write cache size mismatch for buffer "SYSTEM": equipment "Environment" asked for 0, while eqiupment "LED" asked for 10000000
12:51:20.154 2025/02/19 [SC Frontend,ERROR] [mfe.cxx:620:register_equipment,ERROR] Write cache size mismatch for buffer "SYSTEM": equipment "LED" asked for 10000000, while eqiupment "Xenon" asked for 0

I can manually change the write cache size in /Equipment/LED/Common/Write cache size to 0. However, if I delete the LED tree in the ODB, then I get the same problems again. It would be nice if I could either choose the size as 0 in the frontend code, or if the defaults were compatible with our legacy code.

The commit that made the write cache size configurable seems to be from 2019: https://bitbucket.org/tmidas/midas/commits/3619ecc6ba1d29d74c16aa6571e40920018184c0
ELOG V3.1.4-2e1708b5