2249
|
29 Jun 2021 |
Lukas Gerritzen | Bug Report | modbcheckbox behaves erroneous with UINT32 variables | For boolean and INT32 variables, modbcheckbox works as expected. You click, it
sets the variable to true or 1, the checkbox stays checked until you click again
and it's being set back to 0.
For UINT32 variables, you can turn the variable "on", but the checkbox visually
becomes unchecked immediately. Clicking again does not set the variable to
0/false and the tick visually appears for a fraction of a second, but vanishes
again. |
2248
|
29 Jun 2021 |
Marco Francesconi | Suggestion | ODB Load in Sequencer | I just submitted a pull request for this feature, I did quite a lot of testing and it looks good to me.
Let me know if something is not clear.
I'll take care of adding the relevant informations to the wiki once it is merged.
Best,
Marco
> My idea was to collect some feedback instead of blindly submitting code for a pull request.
>
> Currently I'm just calling db_load() with a given file, so it is only supporting .odb formatting.
> It is pretty easy to extend to json by calling the db_load_json() depending on the file extension.
> I do not see a similar call for the .xml format, maybe I can study tomorrow how it is implemented in odbedit and port it to the sequencer.
>
> I guess that the ODBPasteJSON can be a solution as well but I find it a bit too technical.
> Anyway it is easy to implement just by calling db_paste_json(), I will keep this in mind.
>
> I'll try to sort this out and make a commit soon.
> Best,
>
> Marco
>
>
>
> > > ... at MEG, we keep hundreds of XML files for configuration. Mostly historical, but that's how it is.
> >
> > same here, lots of historical .odb and .xml files.
> >
> > I think the .odb and .xml support is here to stay. Best I remember, latest things I fixed in both
> > was support for unlimited string length (and removal of associated buffer overflows). Right now,
> > I am not sure if both are UTF-8 clean and if they properly escape all control characters,
> > something to fix as we go or as we bump into problems.
> >
> > K.O. |
2247
|
28 Jun 2021 |
Marco Francesconi | Suggestion | ODB Load in Sequencer | My idea was to collect some feedback instead of blindly submitting code for a pull request.
Currently I'm just calling db_load() with a given file, so it is only supporting .odb formatting.
It is pretty easy to extend to json by calling the db_load_json() depending on the file extension.
I do not see a similar call for the .xml format, maybe I can study tomorrow how it is implemented in odbedit and port it to the sequencer.
I guess that the ODBPasteJSON can be a solution as well but I find it a bit too technical.
Anyway it is easy to implement just by calling db_paste_json(), I will keep this in mind.
I'll try to sort this out and make a commit soon.
Best,
Marco
> > ... at MEG, we keep hundreds of XML files for configuration. Mostly historical, but that's how it is.
>
> same here, lots of historical .odb and .xml files.
>
> I think the .odb and .xml support is here to stay. Best I remember, latest things I fixed in both
> was support for unlimited string length (and removal of associated buffer overflows). Right now,
> I am not sure if both are UTF-8 clean and if they properly escape all control characters,
> something to fix as we go or as we bump into problems.
>
> K.O. |
2246
|
28 Jun 2021 |
Konstantin Olchanski | Suggestion | ODB Load in Sequencer | > ... at MEG, we keep hundreds of XML files for configuration. Mostly historical, but that's how it is.
same here, lots of historical .odb and .xml files.
I think the .odb and .xml support is here to stay. Best I remember, latest things I fixed in both
was support for unlimited string length (and removal of associated buffer overflows). Right now,
I am not sure if both are UTF-8 clean and if they properly escape all control characters,
something to fix as we go or as we bump into problems.
K.O. |
2245
|
28 Jun 2021 |
Stefan Ritt | Suggestion | ODB Load in Sequencer | > > > > Hi all,
> > > > for my experiment we ended up with the need of changing lot of parameters (~9000 values) in the ODB at once by the sequencer.
> > > > The very first solution was to use a sequencer function with a ton of ODBSET calls, however a more elegant solution may be to provide an "ODBLoad" command which mimics the "load" command of odbedit.
> > > > I already have a working modification to the sequencer for this, if you agree I will commit it to a dedicated brach.
> > > > Let me know if you think this is a good approach.
> > > >
> > >
> > > Sounds like a good idea. I trust you are using the data in json format? Perhaps the command
> > > should be named "ODBLoadJSON" to be clear about this.
> > >
> > > (JSON is preferred over .odb and .xml for many reasons (ask me))
> >
> > What if some experiment keep some files in .xml format (ask me!). The routine should check for the extension and support all three formats.
> >
>
> Yes, hard to tell without seeing his full proposal, including the code. If it is load from file,
> sure we look at the file extension, I think the existing code already would do this and support all 3 formats.
>
> But if he wants to load ODB data from a text literal or from a string,
> we might as well stick to json. I guess we could support the other formats, but I do not see anybody
> using anything other than json for new code like this.
>
> ODBPasteJSON("/foo/bar/baz", '{"var1":1, "var2":"somestr"}');
I agree that if one would paste a string to the ODB, then JSON would be best.
But at MEG, we keep hundreds of XML files for configuration. Mostly historical, but that's how it is.
Stefan |
2244
|
28 Jun 2021 |
Konstantin Olchanski | Suggestion | ODB Load in Sequencer | > > > Hi all,
> > > for my experiment we ended up with the need of changing lot of parameters (~9000 values) in the ODB at once by the sequencer.
> > > The very first solution was to use a sequencer function with a ton of ODBSET calls, however a more elegant solution may be to provide an "ODBLoad" command which mimics the "load" command of odbedit.
> > > I already have a working modification to the sequencer for this, if you agree I will commit it to a dedicated brach.
> > > Let me know if you think this is a good approach.
> > >
> >
> > Sounds like a good idea. I trust you are using the data in json format? Perhaps the command
> > should be named "ODBLoadJSON" to be clear about this.
> >
> > (JSON is preferred over .odb and .xml for many reasons (ask me))
>
> What if some experiment keep some files in .xml format (ask me!). The routine should check for the extension and support all three formats.
>
Yes, hard to tell without seeing his full proposal, including the code. If it is load from file,
sure we look at the file extension, I think the existing code already would do this and support all 3 formats.
But if he wants to load ODB data from a text literal or from a string,
we might as well stick to json. I guess we could support the other formats, but I do not see anybody
using anything other than json for new code like this.
ODBPasteJSON("/foo/bar/baz", '{"var1":1, "var2":"somestr"}');
K.O. |
2243
|
28 Jun 2021 |
Stefan Ritt | Suggestion | ODB Load in Sequencer | > > Hi all,
> > for my experiment we ended up with the need of changing lot of parameters (~9000 values) in the ODB at once by the sequencer.
> > The very first solution was to use a sequencer function with a ton of ODBSET calls, however a more elegant solution may be to provide an "ODBLoad" command which mimics the "load" command of odbedit.
> > I already have a working modification to the sequencer for this, if you agree I will commit it to a dedicated brach.
> > Let me know if you think this is a good approach.
> >
>
> Sounds like a good idea. I trust you are using the data in json format? Perhaps the command
> should be named "ODBLoadJSON" to be clear about this.
>
> (JSON is preferred over .odb and .xml for many reasons (ask me))
What if some experiment keep some files in .xml format (ask me!). The routine should check for the extension and support all three formats.
Stefan |
2242
|
28 Jun 2021 |
Konstantin Olchanski | Suggestion | ODB Load in Sequencer | > Hi all,
> for my experiment we ended up with the need of changing lot of parameters (~9000 values) in the ODB at once by the sequencer.
> The very first solution was to use a sequencer function with a ton of ODBSET calls, however a more elegant solution may be to provide an "ODBLoad" command which mimics the "load" command of odbedit.
> I already have a working modification to the sequencer for this, if you agree I will commit it to a dedicated brach.
> Let me know if you think this is a good approach.
>
Sounds like a good idea. I trust you are using the data in json format? Perhaps the command
should be named "ODBLoadJSON" to be clear about this.
(JSON is preferred over .odb and .xml for many reasons (ask me))
K.O. |
2241
|
28 Jun 2021 |
Stefan Ritt | Suggestion | ODB Load in Sequencer | > Hi all,
> for my experiment we ended up with the need of changing lot of parameters (~9000 values) in the ODB at once by the sequencer.
> The very first solution was to use a sequencer function with a ton of ODBSET calls, however a more elegant solution may be to provide an "ODBLoad" command which mimics the "load" command of odbedit.
> I already have a working modification to the sequencer for this, if you agree I will commit it to a dedicated brach.
> Let me know if you think this is a good approach.
>
> Marco F
How can people judge your modification if they cannot see it? Why don't you make a pull request, so it can be properly reviewed.
Stefan |
2240
|
28 Jun 2021 |
Marco Francesconi | Suggestion | ODB Load in Sequencer | Hi all,
for my experiment we ended up with the need of changing lot of parameters (~9000 values) in the ODB at once by the sequencer.
The very first solution was to use a sequencer function with a ton of ODBSET calls, however a more elegant solution may be to provide an "ODBLoad" command which mimics the "load" command of odbedit.
I already have a working modification to the sequencer for this, if you agree I will commit it to a dedicated brach.
Let me know if you think this is a good approach.
Marco F |
2239
|
25 Jun 2021 |
Konstantin Olchanski | Bug Fix | changes in history plots | I will have to post an example of a scaled plot. I figure everybody forgot how they look like.
K.O.
> We are using the new history formula as a quick way to convert signals from sensors to actual physical values (for example Voltage->Temperature, Voltage->relative humidity
> ...), so it is great that the shown voltage is the calculated one.
>
> I would like to add a point to this discussion.
> In our collaboration people attach images of history plots to elogs, meeting presentation and/or physical logbooks.
> The proposed scaling formula may work fine online using the cursors, but, once an image is created, I do not understand how it is possible to extract the value for a scaled
> variables.
> Suppose you see a graph in a presentation with a current increase by some PSU and the current was scaled to be in the same plot of the voltage.
> Looking at the delta in the image, how can you judge the current increase without any axis/grid to refer to?
>
> So I support Stefan proposal for a secondary axis, as long as it is clear which value belong to which axis.
> Maybe marking the channels in the description or using different line styles/thickness?
>
> Best,
> Marco |
2238
|
25 Jun 2021 |
Konstantin Olchanski | Bug Fix | changes in history plots | > > The only "correct" way in my opinion is to implement two vertical axis, as can be seen in some papers. One for the HV, and a
> > new TBD right axis for the current values, then indicating for each graph if the left or right vertical axis applies. For
> > the secondary axis we can have autoscaling or fixed scaling, as we have for the primary axis.
In the past, we have done some useful plots with maybe 10 variables plotted
at the same time with different scaling and positioning on the graph.
Having 2 vertical axis is maybe useful for the specific case of plotting high voltages,
but not in the general case.
Actually, just 2 vertical axis will not work to plot high voltages in ALPHA-g, because
we have anode currents on the scale 0..0.1 uA and cathode currents on the scale 50..60 uA.
K.O. |
2237
|
25 Jun 2021 |
Konstantin Olchanski | Bug Fix | changes in history plots | > I disagree ...
I am happy with disagreement and differences of opinions. Zest of life, driver of progress and improvements, etc.
I am even more happy with solutions to problems. The current problem is that the offset and factor feature
of history plots has been removed without much discussion.
I stress, we have been using this feature to run experiments for the last 20 years.
I do not understand objections to it being restored. If you do not want to use it, do not use it.
K.O.
> with the proposed change to scale the HV current for a "nice" display. If values are scaled, the axis should be
> scaled in the same way. Otherwise people might read the current from the plot, look at the axis, and again get the wrong
> value (the factor of 25x you mention). Sure you can hover with the cursor over the graph, and see the right value, but think
> of taking a screen shot, putting this into a publication, and get complaints from the reviewer.
>
> The only "correct" way in my opinion is to implement two vertical axis, as can be seen in some papers. One for the HV, and a
> new TBD right axis for the current values, then indicating for each graph if the left or right vertical axis applies. For
> the secondary axis we can have autoscaling or fixed scaling, as we have for the primary axis.
>
> Stefan |
2236
|
25 Jun 2021 |
Konstantin Olchanski | Bug Fix | changes in history plots | > A general warning: With the recent history changes implemented in the develop branch, starting from a fresh ODB and editing
> any history panel, on gets tons of errors and debug output from mhttpd: ...
This is the reason most projects have separate development and production branches.
I recommend everybody to use the released tagged versions of midas for production.
> I strongly recommend to make such modifications on a separate branch not to
> break running experiments.
Is there something that does not work anymore? Did I break something? The debug messages I am still
tuning.
K.O.
>
> MVOdb: Error: MIDAS db_get_value() at ODB path "/History/Display/Default/Trigger rate/Minimum" returned status 312
> MVOdb: Error: MIDAS db_get_value() at ODB path "/History/Display/Default/Trigger rate/Minimum" returned status 312
> MVOdb: Error: MIDAS db_get_value() at ODB path "/History/Display/Default/Trigger rate/Maximum" returned status 312
> MVOdb: Error: MIDAS db_get_value() at ODB path "/History/Display/Default/Trigger rate/Maximum" returned status 312
> MVOdb: Error: MIDAS db_get_value() at ODB path "/History/Display/Default/Trigger rate/Zero ylow" returned status 312
> MVOdb: Error: MIDAS db_get_value() at ODB path "/History/Display/Default/Trigger rate/Log axis" returned status 312
> MVOdb: Error: MIDAS db_get_value() at ODB path "/History/Display/Default/Trigger rate/Zero ylow" returned status 312
> Load from ODB History/Display/Default/Trigger rate: hist plot: 2 variables
> timescale: 1h, minimum: 0.000000, maximum: 0.000000, zero_ylow: 0, log_axis: 0, show_run_markers: 1, show_values: 1,
> show_fill: 1
> var[0] event [System][Trigger per sec.] formula [], colour [#00AAFF] label [] factor 1.000000 offset 0.000000 voffset
> 0.000000 order 10
> var[1] event [System][Trigger kB per sec.] formula [], colour [#FF9000] label [] factor 1.000000 offset 0.000000 voffset
> 0.000000 order 20
>
>
>
> This has to be fixed by the original author. I strongly recommend to make such modifications on a separate branch not to
> break running experiments.
>
> Stefan |
2235
|
25 Jun 2021 |
Marco Francesconi | Bug Fix | changes in history plots | We are using the new history formula as a quick way to convert signals from sensors to actual physical values (for example Voltage->Temperature, Voltage->relative humidity
...), so it is great that the shown voltage is the calculated one.
I would like to add a point to this discussion.
In our collaboration people attach images of history plots to elogs, meeting presentation and/or physical logbooks.
The proposed scaling formula may work fine online using the cursors, but, once an image is created, I do not understand how it is possible to extract the value for a scaled
variables.
Suppose you see a graph in a presentation with a current increase by some PSU and the current was scaled to be in the same plot of the voltage.
Looking at the delta in the image, how can you judge the current increase without any axis/grid to refer to?
So I support Stefan proposal for a secondary axis, as long as it is clear which value belong to which axis.
Maybe marking the channels in the description or using different line styles/thickness?
Best,
Marco |
2234
|
25 Jun 2021 |
Stefan Ritt | Bug Fix | changes in history plots | A general warning: With the recent history changes implemented in the develop branch, starting from a fresh ODB and editing
any history panel, on gets tons of errors and debug output from mhttpd:
MVOdb: Error: MIDAS db_get_value() at ODB path "/History/Display/Default/Trigger rate/Minimum" returned status 312
MVOdb: Error: MIDAS db_get_value() at ODB path "/History/Display/Default/Trigger rate/Minimum" returned status 312
MVOdb: Error: MIDAS db_get_value() at ODB path "/History/Display/Default/Trigger rate/Maximum" returned status 312
MVOdb: Error: MIDAS db_get_value() at ODB path "/History/Display/Default/Trigger rate/Maximum" returned status 312
MVOdb: Error: MIDAS db_get_value() at ODB path "/History/Display/Default/Trigger rate/Zero ylow" returned status 312
MVOdb: Error: MIDAS db_get_value() at ODB path "/History/Display/Default/Trigger rate/Log axis" returned status 312
MVOdb: Error: MIDAS db_get_value() at ODB path "/History/Display/Default/Trigger rate/Zero ylow" returned status 312
Load from ODB History/Display/Default/Trigger rate: hist plot: 2 variables
timescale: 1h, minimum: 0.000000, maximum: 0.000000, zero_ylow: 0, log_axis: 0, show_run_markers: 1, show_values: 1,
show_fill: 1
var[0] event [System][Trigger per sec.] formula [], colour [#00AAFF] label [] factor 1.000000 offset 0.000000 voffset
0.000000 order 10
var[1] event [System][Trigger kB per sec.] formula [], colour [#FF9000] label [] factor 1.000000 offset 0.000000 voffset
0.000000 order 20
This has to be fixed by the original author. I strongly recommend to make such modifications on a separate branch not to
break running experiments.
Stefan |
2232
|
25 Jun 2021 |
Stefan Ritt | Bug Report | my html modbvalue thing is not working? | Can you post your complete page here so that I can have a look?
Stefan |
2231
|
24 Jun 2021 |
Stefan Ritt | Bug Fix | changes in history plots | I disagree with the proposed change to scale the HV current for a "nice" display. If values are scaled, the axis should be
scaled in the same way. Otherwise people might read the current from the plot, look at the axis, and again get the wrong
value (the factor of 25x you mention). Sure you can hover with the cursor over the graph, and see the right value, but think
of taking a screen shot, putting this into a publication, and get complaints from the reviewer.
The only "correct" way in my opinion is to implement two vertical axis, as can be seen in some papers. One for the HV, and a
new TBD right axis for the current values, then indicating for each graph if the left or right vertical axis applies. For
the secondary axis we can have autoscaling or fixed scaling, as we have for the primary axis.
Stefan |
2230
|
24 Jun 2021 |
Konstantin Olchanski | Suggestion | MidasConfig.cmake usage | > > So you say "nuke ${MIDAS_LIBRARIES}" and "fix ${MIDAS_INCLUDE}". Ok.
> A more moderate option ...
For the record, I did not disappear. I have a very short time window
to complete commissioning the alpha-g daq (now that the network
and the event builder are cooperating). To add to the fun, our high voltage
power supply turned into a pumpkin, so plotting voltages and currents
on the same history plot at the same time (like we used to be able to do)
went up in priority.
K.O. |
2229
|
24 Jun 2021 |
Konstantin Olchanski | Bug Fix | changes in history plots | I am updating the history plots. Main changes:
- the old history display code should again be easily usable (use the "open in old history display" checkbox)
- the history plot editor has an "edit in ODB" button that takes as to the plot definition in ODB (sometimes it is
easier to editing things in the ODB editor)
- error in history plot editor that created "formula" entry of incorrect size should be fixed
- "reorder" (and "delete entry") functions in the history plot editor should work again (plus added explanation text)
- "factor" and "offset" restored in the history plot editor
- added the long desired "voffset" to simplify plot scaling and positioning
- (factor, offset and voffset do not yet work in the new history plots, TBI ASAP)
- history plot editor and generate_hist_graph() now use the same code to read plot definitions from ODB. There should
be no more confusion about content of history plot entries in ODB and what each entry is supposed to do.
These changes have been precipitated by our inability to plot high voltage voltage and current on the same plot,
see bug https://bitbucket.org/tmidas/midas/issues/308/history-plot-formula-cannot-be-used-to
Voltage is in the range 0..1000 (volts) and current is in the range 0..50 and 0..0.100, autoscaling on voltage
makes the currents invisible at the zero line. In the past, we used the "factor" setting to scale
the graphs so we can see both voltage and currents at the same time (currents scaled up by factor 25 and 600,
as example).
The new "formula" feature was supposed to replace (and improve upon) the "factor" and "offset". But if I use
the formula "x*25", suddenly the plot is telling us that current values are not 50 uA, but 1250 uA (50*25),
and this is just wrong. We do not want to scale the micro-amps, we want to better position the plot on the graph,
like the old "factor" and "offset" allowed us to do.
So the idea is to use this computation:
y_position_on_plot = offset + factor*(formula(history_value) - voffset)
- "formula" is to transform history values into physical values (i.e. pressure meter reports bars, but we want atm, or
voltmeter is reading in discrete units of 0.125V, we want to see volts)
- "factor" and "offset" is to position the graphs on the plot for best visual presentation of data
- I also added is the much desired "voffset", you only know it is needed if you have a non-zero "offset" and you need
to change the "factor", surprise, "offset" has ot be changed, too, and good luck recalculating it correctly in one
try.
The way to use this stuff:
- adjust "voffset" to bring the graph to around y=0
- increase the "factor" to zoom-in on features and stuff
- adjust "offset" to move the graph up and down relative to all the other graphs on the plot
- now one can zoom in and out as needed by changing the "factor" and the plot will stay roughly in the right place
without having to readjust the offsets.
K.O. |
|